The 460-15-100-LLS is a liquid level sensor to detect the presence of conductive liquids. A probe is mounted at the desired tank level and connected to the Littelfuse pump control. When the probe is submersed, the relay's output contacts will change state as soon as the debounce time expires. The adjustable debounce timer is intended to prevent nuisance actuating due to waves or splashing in the tank.

Relay logic can be inverted so the relay's output contacts change state when the probe is no longer submersed. This makes the unit versatile for use in pump-up and pump-down applications.

商品仕様、各種認証情報、在庫のご確認、部品のご注文は以下をご覧ください

Catalog #Input
Voltage (V)
Output
Form
Termination TypeMounting MethodDimensionsWeight (lbs/g)HumidityInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Protection ClassSense VoltageSensitivity (Ohms)Storage Temperature (F/C)Stock
カタログ番号入力
電圧 (V)
出力
フォーム
端子タイプ取付け方式寸法重量 (ポンド / g)湿度Input AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Protection ClassSense Voltage感度(オーム)保管温度 (F/C)在庫
460-15-100-LLS 110 - 120 Vac nominalDPST - 2 Form ATorque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG35mm DIN rail or Surface Mount (#6 or #8 screws)3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm)0 Kg10 - 95% non-condensing per IEC 68-2-350 / 60 (50 will increase all delay timers by 20%)2Pilot Duty: 360 VA @ 240 Vac B300; General Purpose: 8 A @ 240 VacIP20; NEMA 1 (finger safe)5 Vdc continuous (probe)100-40° to 80°C (-40° to 176°F)確認